Stationary Batteries OGi

Reliable non-sealed OGi batteries are used in power supply systems at thermal power plants, continuous power supply systems, and emergency power supply systems.
Description
OGi batteries can be used for both long-term low current discharge (about 10 hours) and short-term discharge (about 2-10 minutes).
The versatility of OGi batteries allows them to be used in both large-scale electrical power systems and small off-grid installations.
Characteristics
- Technology
- Liquid electrolyte
- Purpose
- SOPT of powerful power plants, industrial enterprises, railway infrastructure
- Features
- Long service life, high discharge currents
- Voltage
- 110-220V
- Capacity
- 25 - 600 Ah
- Number of Cycles
- 1000-1200
List of Models
| Utilization Coeff. of Energy/Element | 1.8 | EN/IEC 60896-11 | Dimensions | Weight | |||
|---|---|---|---|---|---|---|---|
| Discharge (h) | 10 | Resistance | Current | Length | Width | Height | Coll. |
| Element Type | Nom. Capacity | mΩ | А | mm | mm | mm | kg |
| 2V 6 OGi 150 | 165 | 0.5 | 3960 | 420 | 103 | 206 | 14.4 |
| 2V 10 OGi 250 | 270 | 0.3 | 6650 | 420 | 124 | 206 | 21.3 |
| 2V 14 OGi 350 | 373.3 | 0.21 | 8960 | 420 | 145 | 206 | 30 |
| 2V 6 OGi 480 | 490 | 0.3 | 6700 | 700 | 145 | 206 | 43 |
| 2V 24 OGi 600 | 684 | 0.13 | 16420 | 392 | 205 | 272 | 93 |
Scope of Application